Lightning arrester set for TT and TNS networks - Lightning arrest for power supply 125kA MCD 50-B...

MCD 50-B 3+1 5096879 4012195077091 EAN/GTIN DE 64419409 WEEE

Our best price
£417.47 incl. VAT (£0.00)
£845.69 (-50.64% RRP***)

3-5 days* (GBR)

Safety and hazard information
Please note that electrotechnical work may only be carried out by qualified electricians or under their guidance and supervision. Observe any deviating country-specific electrical installation standards and regulations and seek advice from a local electrician.In addition, observe more current safety instructions and regulations for the products on the manufacturer's side or the product descriptions and installation instructions on the manufacturer's side.

Devices with a connected load of > 380V/400V require a heavy current connection and may only be connected by an approved electrical company. Devices with a power rating > 12kW require the approval of your grid operator (Germany, other countries may differ).
read more
show less
Lightning arrester set for TT and TNS networks MCD 50-B 3+1 lightning impulse current (10/350 µs)... more
Lightning arrester set for TT and TNS networks - Lightning arrest for power supply 125kA MCD 50-B... – OBO – 5096879 – 4012195077091: Lightning arrester set for TT and TNS networks MCD 50-B 3+1 lightning impulse current (10/350 µs) 125kA, nominal discharge current (8/20) 125kA, maximum continuous voltage AC 255V, nominal voltage AC 230V, protection level 1.3kV, follow current extinguishing capacity 25kA, Type of mounting DIN rail TH35, size 8 HP, signaling on the device without, test class type 1, combi/lightning arrester set MCD... type 1+2 according to EN 61643-11. MCD 50-B/3+1: (4-pin) for use in 230/400 V TT and TN-S systems. Energetically coordinated to type 2 arresters and directly to end devices. Innovative multi-carbon technology with pluggable, encapsulated spark gaps. Corresponds to the VDN guideline 2nd edition 2004, discharge capacity 50kA 10/350µs per pole, mains follow current extinguishing 10 kA max. required back-up fuse 500 A, LPZ 0-2. The low protection level (Up <1.7 kV) eliminates the need to install decoupling inductors and provides protection directly to the end device. The arrester set is supplied complete, ready for connection and pre-installed. An application example: industrial feeds and buildings with lightning protection systems. 5 year warranty
... more
Network form DC no
Network form IT no
Network shape TN yes
Mains form TN-C no
Mains form TN-CS yes
Mains form TN-S yes
Network shape TT yes
Network form other no
Lightning impulse current (10/350 µs) 50 kA
Nominal discharge current (8/20) 50 kA
Highest continuous voltage AC 255V
Rated voltage AC 230V
Protection level 1.7 kV
Protection level LN 1.7 kV
Follow current extinguishing capability 0.1 kA
Mounting DIN rail TH35
Size 8 TE
With telecommunication contact no
Blow out no
Signaling on the device without
Test class type 1 yes
IP protection) IP20

Rate item

(0 reviews)
Read, write and discuss reviews... more
Customer review for "Lightning arrester set for TT and TNS networks - Lightning arrest for power supply 125kA MCD 50-B..."
Write a review
Evaluations will be activated after verification.
Please enter these characters in the following text field.

The fields marked with * are required.